Vibronic
Point level detection
Liquiphant FTL51C
Point level switch for liquids with highly corrosion-resistant coating
Liquiphant FTL51C is a point level switch with extension tube and highly corrosion resistant coating. For use in hazardous areas with all international certificates. Useable in all industries. FTL51 offers functional safety SIL2/SIL3. With the second line of defense highest degree of safety and availability of the device can be guaranteed. Reliable measurement values, not affected by: changing media properties, flow, turbulences, gas bubbles, foam, vibrations or build-up.
-
Voordelen
Use in safety systems requiring functional safety to SIL2/SIL3 in accordance with
IEC 61508/IEC 61511-1Different plastic coating (PFA) and enamel coating for applications with aggressive medias
International explosion protection certificates and overfill...
-
Toepassingsgebied
Point level switch for all liquids with highly corrosion-resistant coating.
Process connections: Flanges and hygienic process connection (FDA conform with PFA)
Temperature: -50 to +150°C (-58 to +302°F)
Pressure: -1 to +40bar (-14.5 to +580psi)
Sensor...
Documenten / handleidingen / software
-
Technical Information
Liquiphant M Density and Density Computer
FML621
Density computer for liquids
Also for use in hazardous areasTechnische informatie (TI) -
Liquiphant M
FTL51C
Technical Information
Point level switch for all kinds of liquids
with high corrosion-resistant coatingTechnische informatie (TI) -
Bedienungsanleitung/ Operating Instuction Liquiphant.
Sliding Sleeve
Inbedrijfsstellingsvoorschriften (BA) -
Liquiphant M/S
FTL50, FTL51, FTL50H, FTL51H, FTL51C, FTL70,
FTL71
Electronic insert FEL50A PA
Vibration Limit Switch
Level limit switch for all liquids.
Suitable for use in hazardous areas, food and pharmaceuticalsInbedrijfsstellingsvoorschriften (BA) -
Liquiphant M Density FTL51C
Operating Instructions
Liquiphant M for density and concentration calculation
Short Instruction (KA)06/16Duits , Engels , Spaans , fr , Italiaans , Nederlands -
Exchange of sensor on Liquiphant M/S
Exchange of sensor on Liquiphant M/S
Short Instruction (KA)04/12Duits , Engels -
Bedienungsanleitung/ Operating Instuctions Liquiphant M/S + FEL57
Selbsttest
Self testShort Instruction (KA)02/17Duits , Engels , Spaans , fr , Italiaans , Nederlands -
Liquiphant M FTL50, FTL51
Operating Instructions
Point level switch for all kinds of liquids
Short Instruction (KA)01/17Duits , Engels , Spaans , fr , Italiaans , Nederlands -
Liquiphant M
FTL51C-
7
Operating
Instructions
Point level switch for all liquids
With highly corrosion-resistant coating and aluminium
housing.Short Instruction (KA)01/17Duits , Engels , Spaans , fr , Italiaans , Nederlands -
Liquiphant M FTL51C
Operating Instructions
Point level switch for all kinds of liquids with high
corrosion-resistant coatingShort Instruction (KA)01/17Duits , Engels , Spaans , fr , Italiaans , Nederlands -
Cover for housing T13 electronic compartment with sight glas
Installation instruction
Liquicap M, Solicap M, Liquphant M/S/FailSafe, Soliphant M
Installatievoorschriften (EA) -
Cover for housing T13 terminal compartment
Installation instruction
Liquiphant M/S, Soliphant M, Liquicap M, Solicap M/S
Installatievoorschriften (EA) -
Cover for Housing F15
Installation instruction
LIquiphant M/S/Fail Safe, Soliphant M, Cerabar M, Deltapilot M
Installatievoorschriften (EA) -
Cover for housing T13 electronic compartment
Installation instruction
Liquiphant M/S, Soliphant M, Liquicap M, Solicap M/S
Installatievoorschriften (EA) -
Cover for housing F13
Installation instruction
Liquiphant M/S, Soliphant M, Liquicap M, Solicap M/S
Installatievoorschriften (EA) -
Cover for Housing F17
Installation instruction
LIquiphant M/S/Fail Safe, Soliphant M
Installatievoorschriften (EA) -
Cover for Housing F16
Installation instruction
LIquiphant M/S/Fail Safe, Soliphant M
Installatievoorschriften (EA) -
Diagnostics plug
Installation instruction
Liquiphant M/S/FailSafe, Soliphant T/M
Installatievoorschriften (EA) -
Cover for housing F27
Installation instruction
Liquihant M/S, Soliphant M, Liquicap M, Solicap M/S
Installatievoorschriften (EA) -
Graphite gaskets
Installation instruction
Liquiphant M, LIquiphant S, Liquiphant FailSafe
Installatievoorschriften (EA) -
Safety Instructions
Liquiphant M
FTL50(H), FTL51(H), FTL51C
PROFIBUS PA
II 1 G Ex ia IIC T3...T6 Ga
II 1 G Ex ia IIB T3...T6 Ga
KEMA 99 ATEX 5172 XEx Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M
FTL51C
ATEX: II 1/2 G Ex ia IIC T6 Ga/Gb
IECEx: Ex ia IIC T6 Ga/Gb
KEMA 99 ATEX 0523 X; IECEx DEK 15.0028XEx Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
EAC:
Ga/Gb Ex de IIC/IIB T6...T3
Ga/Gb Ex de IIC T6...T1
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M, Liquiphant S
FTL50(H)/51(H)/51C, FTL70/71
ATEX: II 1/2 G Ex d IIC T2...T6 Ga/Gb,
II 1/2 G Ex d IIC/IIB T3...T6 Ga/Gb
IECEx: Ex d IIC T2...T6 Ga/Gb,
Ex d IIC/IIB T3...T6 Ga/Gb
KEMA 10 ATEX 0113 X; IECEx KEM 10.0047 XEx Veiligheidsinstructies (XA) -
Liquiphant M FTL50(H), FTL51(H), FTL51C
JPN:
Ex db IIB T3 Ga/Gb
Ex db IIC T3 Ga/Gb
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M/S FTL50/51(H), FTL51C, FTL70/71
Ex d IIC/IIB T3...T6 Ga/Gb
Ex d IIC T2...T6 Ga/Gb
TÜV 13.0900 X (INMETRO)Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
FM
Drawing No.: 960392-1060 J
Drawing Type: Control DrawingEx Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
EAC:
Ga/Gb Ex ia IIC/IIB T6...T3 X
Ga/Gb Ex ia IIC T6...T2 X
Ex ia IIIC T80°C Da/Db X
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
Approval No.: KEMA 02 ATEX 2169
ATEX II 1/2 G
Protection:
EEx d IIC T2...T6
EEx d IIB T3...T6Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M
FTL51C
ATEX: II 1/2 G Ex db eb IIC T6...T3 Ga/Gb
IECEx: Ex db eb IIC T6...T3 Ga/Gb
DEKRA 15 ATEX 0088; IECEx DEK 15.0060Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
Approval No.: KEMA 99 ATEX 0523
ATEX II 2 G
Protection:
EEx ia/ib IIC T2...T6
EEx ia/ib IIB T3...T6Ex Veiligheidsinstructies (XA) -
Liquiphant M FTL50(H), FTL51(H), FTL51C
JPN:
Ex ia IIC T3 Ga/Gb
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M/S FTL50/51(H), FTL51C, FTL70/71
PROFIBUS PA
Ex ia IIC/IIB T3...T6 Ga/Gb
Ex ia IIC T2...T6 Ga/Gb
Ex ia IIIC T80°C da/Db
TÜV 13.0898 X (INMETRO)Ex Veiligheidsinstructies (XA) -
Liquiphant M FTL51C
ATEX:
II 1/2 G Ex db IIC T6...T3 Ga/Gb
IECEx:
Ex db IIC T6...T3 Ga/Gb
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M/S FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
Ex ia IIC T6 Ga/Gb
Ex ia IIB T6 Ga/Gb
Ex iaD 20/21 T80
GYJ16.1419 (NEPSI)Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M, Liquiphant S
FTL50(H)/51(H)/51C, FTL70/71
ATEX: II 1/2 G Ex db eb IIC T6...T1 Ga/Gb, II 1/2 G Ex db eb IIC/IIB
T6...T3 Ga/Gb
IECEx: Ex db eb IIC T6...T1 Ga/Gb, Ex db eb IIC/IIB T6...T3 Ga/Gb
DEKRA 15 ATEX 0088; IECEx DEK 15.0060Ex Veiligheidsinstructies (XA) -
Liquiphant M FTL51C
EAC:
Ga/Gb Ex d IIC T6...T3
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
Approval No.: KEMA 99 ATEX 1157
ATEX II 2 G
Protection:
EEx d IIC T2...T6
EEx d IIB T3...T6Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C, FTL70/71
Ex d IIC T6...T1 Ga/Gb
Ex d IIC/IIB T6...T3 Ga/Gb
GYJ16.1468X, GYJ16.1469X (NEPSI)Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M/S FTL50/51(H), FTL51C, FTL70/71
Ex ia IIC/IIB T3...T6 Ga/Gb
Ex ia IIC T2...T6 Ga/Gb
Ex ia IIIC T80°C Da/Db
TÜV 13.0898 X (INMETRO)Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S FTL50(H)/51(H)/51C, FTL70/71
NEPSI:
Ex nC IIC T6 Gc
Ex nA IIC T6 Gc
Ex ic IIC T6 Gc
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Liquiphant M FTL50(H), FTL51(H), FTL51C
Liquiphant S FTL70, FTL71
Explosion proof Class I, Div. 1, Groups A, B, C, D
Class II, Div. 1, Groups E, F, G
Class III
cCSAus / XPEx Veiligheidsinstructies (XA) -
II 1/2 G Ex ia IIC T6 Ga/Gb
Veiligheidsinstructies
Liquiphant M,Liquiphant S
FTL50(H)/51(H)/51C,FTL70/71Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
Approval No.: KEMA 02 ATEX 2169
ATEX II 1/2 G
ATEX II 1/2 D IP65 T80°C
Protection:
Ex ia IIC T2...T6
Ex ia IIB T3...T6Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
CSA
Drawing No.: 960009587 A
Drawing Type: Control Drawing
ISEx Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
Approval No.: KEMA 02 ATEX 2169
ATEX II 1/2 G
Protection:
EEx de IIC T2...T6
EEx de IIB T3...T6Ex Veiligheidsinstructies (XA) -
Liquiphant M/S
FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
FM
Drawing No.: 960009203 A
Drawing Type: Control DrawingEx Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S FTL50(H)/51(H)/51C, FTL70/71
ATEX:
II 3 G Ex nA IIC T6 Gc
II 3 G Ex nC IIC T6 Gc
II 3 G Ex ic IIC T6Gc
II 3 D Ex tc IIIC T85°C Dc
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M/S FTL50/51(H), FTL51C, FTL70/71
Ex de IIC/IIB T3...T6 Ga/Gb
Ex de IIC T2...T6 Ga/Gb
TÜV 13.0895 X (INMETRO)Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M, Liquiphant S
FTL50(H)/51(H)/51C, FTL70/71
PROFIBUS PA
ATEX: II 1/2 G Ex ia IIC/IIB T6 Ga/Gb
II 1/2 D Ex ia IIIC T80°C Da/Db
IECEx: Ex ia IIC T6 Ga/Gb
KEMA 99 ATEX 0523; IECEx TUN 04.0017Ex Veiligheidsinstructies (XA) -
Liquiphant M FTL51C
EAC:
Ga/Gb Ex de IIC T6...T3
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
cCSAus Control Drawing
960392-2060 I (EHC: 960005121)
ISEx Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
ATEX:
II 1/2 G Ex db IIC T6...T1 Ga/Gb
II 1/2 G Ex db IIC/IIB T6...T3 Ga/Gb
IECEx:
Ex db IIC T6...T1 Ga/Gb
Ex db IIC/IIB T6...T3 Ga/Gb
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Liquiphant M FTL51C
EAC:
Ga/Gb Ex ia IIC T6...T3 X
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M
FTL50,FTL50H,FTL51H
ATEX: II 1 G Ex ia IIC T6 Ga
IECEx: Ex ia IIC T6 GaEx Veiligheidsinstructies (XA) -
Liquiphant M/S
FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
FM
Drawing No.: 960392-1066 D
Drawing Type: Control DrawingEx Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
Approval No.: EG 01 007-a
ATEX II 3 G
ATEX II 3 D T85°C
Protection:
EEx nL IIC T6Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
Approval No.: KEMA 99 ATEX 0523
ATEX II 1/2 G
Protection:
EEx ia/ib IIC T2...T6
EEx ia/ib IIB T3...T6Ex Veiligheidsinstructies (XA) -
Liquiphant M, Liquiphant S FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
EAC:
Ga/Gb Ex d IIC/IIB T6...T3
Ga/Gb Ex d IIC T6...T1
Safety Instructions
Vibronic Limit Switches, Liquids
Ex Veiligheidsinstructies (XA) -
Safety Instructions
Liquiphant M
FTL51C
PROFIBUS PA
II 1/2 G Ex ia IIC T3...T6 Ga/Gb
KEMA 00 ATEX 1071 XEx Veiligheidsinstructies (XA) -
Liquiphant M FTL50(H), FTL51(H), FTL51C
Liquiphant S FTL70, FTL71
WHG
Allgemeine bauaufsichtliche Zulassung
Z-65.11-230 (DIBt)Certificaat (ZE) -
Liquiphant M FTL50(H), FTL51(H), FTL51C (Leckage)
Allgemeine bauaufsichtliche Zulassung
Z-65.40-446 (DIBt)Certificaat (ZE) -
RFID TAG
Certificate/Declaration of Conformity
ATEX:
II 2 G Ex ia IIC T6 Gb
II 2 D Ex ia IIIC T80°C Db;
IECEx:
Ex ia IIC T6 Gb
Ex ia IIIC T80°C Db
IECEx EPS 15.0042X; EPS 15 ATEX 1 1011 XCertificaat (ZE) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
CSA
Drawing No.: 960392-2060 G
Drawing Type: Control Drawing
ISCertificaat FM/CSA (ZD) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
CSA
Drawing No.: 960392-2060 F
Drawing Type: Control DrawingCertificaat FM/CSA (ZD) -
Liquiphant M/S
FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
FM
Drawing No.: 960392-1066 C
Drawing Type: Control DrawingCertificaat FM/CSA (ZD) -
Liquiphant M/S
FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
FM
Drawing No.: 960392-1066 B
Drawing Type: Control Drawing
NICertificaat FM/CSA (ZD) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
CSA
Drawing No.: 960008826 A
Drawing Type: Control Drawing
XPCertificaat FM/CSA (ZD) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
FM
Drawing No.: 960392-1060 E
Drawing Type: Control DrawingCertificaat FM/CSA (ZD) -
Liquiphant M/S
FTL50(H), FTL51(H), FTL51C, FTL70, FTL71
FM
Drawing No.: 960009203 -
Drawing Type: Control DrawingCertificaat FM/CSA (ZD) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
FM
Drawing No.: 960392-1060 H
Drawing Type: Control DrawingCertificaat FM/CSA (ZD) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
FM
Drawing No.: 960392-1060 I
Drawing Type: Control DrawingCertificaat FM/CSA (ZD) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
CSA
Drawing No.: 960008826 -
Drawing Type: Control Drawing
XPCertificaat FM/CSA (ZD) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
CSA
Drawing No.: 960009587 -
Drawing Type: Control Drawing
ISCertificaat FM/CSA (ZD) -
Liquiphant M, Liquiphant S
FTL50(H), FTL51(H), FTL51C,
FTL70, FTL71
CSA
Drawing No.: 960392-2060 D
Drawing Type: Control DrawingCertificaat FM/CSA (ZD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x + Nivotester FTL325N
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S with FEL51
Functional safety manual (SIL)
Level limit switch for all liquids. Suitable for use in hazardous areas,
food and
pharmaceuticalsSpeciale Documentatie (SD) -
Liquiphant M/S with electronic insert FEL57 + Nivotester FTL325P
Functional Safety Manual
Special Documentation
Point level measuring system
Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S with FEL54
Functional safety manual (SIL)
Level limit switch for all liquids. Suitable for use in hazardous areas,
food and
pharmaceuticals.Speciale Documentatie (SD) -
Weld-in adapter G1, G3/4
Special Documentation
Weld-in adapter G1, G3/4
Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S with electronic insert FEL58 + Nivotester FTL325N
Functional Safety Manual
Special Documentation
Point level measuring system
Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x + Nivotester FTL325P
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Handbook for Functional Safety (SIL)
Liquiphant M/S with FEL56
and Nivotester FTL325N
Level limit switch for all liquids.
Suitable for use in
hazardous areas, food and pharmaceuticals.Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S with FEL55
Functional safety manual (SIL)
Minimum detection (also dry running protection) of all types of liquids
Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S with FEL51
Functional safety manual (SIL)
Dry running protection or operating minimum detection of all types of
liquidsSpeciale Documentatie (SD) -
Functional Safety Manual (SIL)
Liquiphant M/S with FEL57 and
FTL325P
Level limit switch for all liquids.
Suitable for use in hazardous areas, food and pharmaceuticalsSpeciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S with electronic insert FEL56 + Nivotester FTL325N
Functional Safety Manual
Special Documentation
Point level measuring system
Speciale Documentatie (SD) -
Functional safety manual (SIL)
Liquiphant M/S with FEL58 and Nivotester FTL325N
Minimum detection (also dry running protection) of all types of liquids.
Speciale Documentatie (SD) -
Functional safety manual (SIL)
Liquiphant M/S with FEL58 and
Nivotester FTL325N
Overfill protection or maximum detection of all types of liquids.
Speciale Documentatie (SD) -
Handbook for Functional Safety (SIL)
Liquiphant M/S with FEL56 and Nivotester FTL325N
Minimum detection (also dry running protection) of all types of liquids.
Speciale Documentatie (SD) -
Functional safety manual (SIL)
Liquiphant M FTL5, FTL7 with Nivotester FTL325P
Level limit switch for all liquids.
Suitable for use in hazardous areas, food and pharmaceuticalsSpeciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x + Nivotester FTL325P
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x + Nivotester FTL325N
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x + Nivotester FTL325N
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S with FEL52
Functional safety manual (SIL)
Dry running protection or operating minimum detection of all types of
liquidsSpeciale Documentatie (SD) -
Liquiphant M/S with FEL54
Functional safety manual (SIL)
Dry running protection or operating minimum detection of all types of
liquids.Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S with FEL55
Functional safety manual (SIL)
Level limit switch for all liquids. Suitable for use in hazardous areas,
food and
pharmaceuticalsSpeciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x + Nivotester FTL375P
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S FTL5x(H), FTL51C, FTL7x + Nivotester FTL325N
Functional Safety data sheet / Datenblatt zur Funktionalen Sicherheit
Speciale Documentatie (SD) -
Liquiphant M/S with FEL52
Functional safety manual (SIL)
Level limit switch for all liquids. Suitable for use in hazardous areas,
food and pharmaceuticalsSpeciale Documentatie (SD) -
RFID TAG
Special Documentation
RFID TAG
Special DocumentationSpeciale Documentatie (SD) -
Functional Safety Manual (SIL)
Liquiphant M/S and Nivotester
FTL375P
Overspill protection or operating maxi-mum detection of all types of
liquids in
tanks or piping to satisfy particular safety
systems requirements to IEC 61508 or
DIN V 19250.Speciale Documentatie (SD) -
PRM FOUNDATION fieldbus Package V1.05.00
Manufacturer Information includes PRM - Device List, Release Notes –
FOUNDATION fieldbus
Manufacturer Information for users regarding software updates
(following the NAMUR recommendation 53)
New software version: 1.05.00Fabrikanten Informatie (MI) -
Simatic PDM HART Package 1.14.00
Manufacturer Information includes PDM - Device List, Release Notes –
HART
Manufacturer Information for users regarding software updates
(following the NAMUR recommendation 53)
New software version: 1.14.00Fabrikanten Informatie (MI) -
Simatic PDM PROFIBUS Package V1.12.00
Manufacturer Information includes PDM - Device List, Release Notes –
PROFIBUS
Manufacturer Information for users regarding software updates
(following the NAMUR recommendation 53)
New software version: 1.12.00Fabrikanten Informatie (MI) -
AMS FOUNDATION fieldbus Package V1.06.00
Manufacturer Information includes AMS - Device List, Release Notes –
FOUNDATION fieldbus
Manufacturer Information for users regarding software updates
(following the NAMUR recommendation 53)
New software version: 1.06.00Fabrikanten Informatie (MI) -
AMS HART Package V1.12.00
Manufacturer Information includes AMS - Device List, Release Notes –
HART
Manufacturer Information for users regarding software updates
(following the NAMUR recommendation 53)
New software version: 1.12.00Fabrikanten Informatie (MI) -
PRM HART Package V1.08.00
Manufacturer Information includes PRM - Device List, Release Notes –
HART
Manufacturer Information for users regarding software updates
(following the NAMUR recommendation 53)
New software version: 1.08.00Fabrikanten Informatie (MI) -
kurier 01-2014
Kundenmagazin: Ihr Partner für mehr Anlagensicherheit
Klantentijdschrift (CM)01/14Duits -
Juice application: Juice pasteuriser, Application 8
Meas. point 7: level switch deaerator
Industrieoplossingen (SO)Engels -
Juice application: Raw juice, Application 3
Meas. point 3: dry run protection raw juice pump
Industrieoplossingen (SO)Engels -
Juice application: Juice concentration, Application 4
Meas. point 4: level switch evaporator
Application 1: LiquiphantIndustrieoplossingen (SO)Engels -
Brewery application: Brewhouse, Application 6
Meas. point 5: level switch mash and wort vessel
Industrieoplossingen (SO)Engels -
Brewery application: Filling, Application 7
Meas. point 4: level switch KEG unit
Industrieoplossingen (SO)Engels -
Brewery application: Fermentation and Maturation, Application 13
Meas. point 10: level switch leakage vessel
Industrieoplossingen (SO)Engels -
Juice application: CIP unit, Application 5
Meas. point 4: level switch CIP-tank
Application 1: LiquiphantIndustrieoplossingen (SO)Engels -
Juice application: CIP unit, Application 11
Meas. point 9: dry run protection CIP pump
Industrieoplossingen (SO)Engels -
Brewery application: Brewhouse, Application 12
Meas. Point 10: level switch collecting vessel lautertun
Industrieoplossingen (SO)Engels -
Juice application: Mixing continuous, Application 5
Meas. point 5: dry run protection concentrate pump
Industrieoplossingen (SO)Engels -
Brewery application: Fermentation and Maturation, Application 8
Meas. point 6: level switch fermentation and maturation tanks
Industrieoplossingen (SO)Engels -
Dairy application: CIP unit, Application 11
Meas. point 9: dry run protection CIP pump
Industrieoplossingen (SO)Engels -
Juice application: Concentrate storage, Application 2
Meas. point 1: level switch concentrate tanks
Application 2: LiquiphantIndustrieoplossingen (SO)Engels -
Juice application: Mixing batch, Application 5
Meas. point 4: level switch mixing tank
Industrieoplossingen (SO)Engels -
Brewery application: CIP unit, Application 5
Meas. point 4: level switch CIP-tank
Application 1: LiquiphantIndustrieoplossingen (SO)Engels -
Dairy application: Milk storage, Application 5
Meas. point 3: level switch raw milk storage tank
Application 2: LiquiphantIndustrieoplossingen (SO)Engels -
Brewery application: Filtration and Stabilisation, Application 7
Meas. point 7: level switch candle filter
Industrieoplossingen (SO)Engels -
Dairy application: Milk reception, Application 5
Meas. point 3: pH measuring during milk reception
Industrieoplossingen (SO)Engels -
Brewery application: CIP unit, Application 11
Meas. point 9: dry run protection CIP pump
Industrieoplossingen (SO)Engels -
Juice application: Concentrate storage, Application 8
Meas. point 5: dry run protection concentrate pump
Industrieoplossingen (SO)Engels -
Dairy application: CIP unit, Application 5
Meas. point 4: level switch CIP-tank
Application 1: LiquiphantIndustrieoplossingen (SO)Engels -
Dairy application: Milk reception, Application 2
Meas. point 1: level switch deaerator
Application 2: LiquiphantIndustrieoplossingen (SO)Engels -
Mesure de niveau
Aperçu des produits pour des applications dans des liquides et des
solides en vracBranches (FA)03/19fr -
Füllstandmesstechnik
Produktübersicht für Anwendungen in Flüssigkeiten und Schüttgütern
Branches (FA)03/17Duits -
Level measurement
Product overview for applications in liquids and bulk solids
Branches (FA)03/17Engels -
Catálogo Medición y Detección de nivel
Gama de productos para aplicaciones con líquidos y sólidos
Branches (FA)03/17Spaans -
Level measurement
Product overview for applications in liquids and bulk solids
Branches (FA)03/17Engels -
Solutions in tanker loading
Protect your profit, protect your people
Competentie Brochure (CP)08/13Engels -
The Liquiphant family
Point level detection in liquids using the vibronic measuring principle
Competentie Brochure (CP)07/16Engels -
Die Liquiphant-Familie
Grenzstanddetektion in Flüssigkeiten mit dem Messprinzig Vibronik
Competentie Brochure (CP)07/16Duits -
GSD Single, GSD_EH_PA_LE_Liquiphant_0x152B_V01_00_PALIB, 14.04.2014 (Leve
l, Liquiphant, 0x152B)
PROFIBUS PA,
PROFIBUS System Version: AnyGeneral Station Description (GSD)1.00.00Language neutral -
EDD Single, PDM_PA_LE_Liquiphant_0x152B_0x01_0x02, 07.01.2019 (Level, Liquiphant, 0x152B)
PROFIBUS PA,
PDM Version: 6.0 SP5Electronic Data Description (EDD)1.00.00Language neutral -
EDD Single, PDM_PA_LE_Liquiphant_0x152B_0xna_0x02, 20.12.2016 (Level, Liquiphant, 0x152B)
PROFIBUS PA,
PDM Version: 8.1, 9.1Electronic Data Description (EDD)1.0.0.0Language neutral -
DTM Single, LiquiphantM_S_FTL5x_7x_PA_V1_3, 09.07.2019 (Level, Liquiphant, 0x152B)
PROFIBUS PA,
DeviceCare Version: 1.06.00
Field Xpert - SMT70 Version: 1.03.00
FieldCare Version: 2.13.00Device Type Manager (DTM)1.5.153.348Language neutral -
DTM Single, LiquiphantM_S_FTL5x_7x_PA_V1_0___V1_2, 09.07.2019 (Level, Liquiphant, 0x152B)
PROFIBUS PA,
DeviceCare Version: 1.06.00
Field Xpert - SMT70 Version: 1.03.00
FieldCare Version: 2.13.00Device Type Manager (DTM)1.5.153.348Language neutral -
Animation Messprinzip Vibronik
Animation DE mp4 1280x720
Animatie10/12Duits -
Animation Messprinzip Vibronik
Animation DE flv 480x270
Animatie10/12Duits -
Measuring Principle Vibronic
Animation EN mp4 1280x720
Animatie09/12Engels -
Measuring Principle Vibronic
Animation EN flv 480x270
Animatie09/12Engels -
Animation Measuring Principle Vibronic FR
Animation FR flv 480x270
Animatie05/13fr -
Animation Measuring Principle Vibronic FR
Animation FR mp4 1280x720
Animatie05/13fr -
Measuring Principle Vibronic
Animation ES mp4 1280x720
Animatie05/13Engels -
Measuring Principle Vibronic
Animation ES flv 480x270
Animatie05/13Spaans -
Measuring Principle Vibronic
Animation IT flv 480x270
Animatie01/13Italiaans -
Measuring Principle Vibronic
Animation IT mp4 1280x720
Animatie01/13Italiaans -
Measuring Principle Vibronic
Animation TR mp4 1280x720
Video08/17Turks -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
verklaring Number: HE_00725_01.17Manufacturer DeclarationDuits , Engels -
Liquiphant M
Productcode: FTL51C-
verklaring Number: HE_00813_01.17
Specificatie van de fabrikant: RoHSManufacturer DeclarationChinees -
Liquiphant M
Productcode: FTL51C-
verklaring Number: HE_00808_01.17
Specificatie van de fabrikant: RoHSManufacturer DeclarationChinees -
Cerabar S, Liquiphant M, Cerabar M, Deltapilot M, Deltapilot S
Productcode: PMP75-, FMB70-, PMP55-, PMP51-, PMC51-, FTL51-, FTL51H-, FTL51C-, FTL50H-, FTL50-, FMB50-
verklaring Number: FDA_00073_04.15FDA DeclarationDuits , Engels -
Liquiphant M
Productcode: FTL51C-
verklaring Number: FDA_00216_01.19FDA DeclarationDuits , Engels -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
verklaring Number: EC_00565_03.17EU DeclarationDuits , Engels , fr -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
verklaring Number: EC_00560_03.17EU DeclarationDuits , Engels , fr -
Liquiphant M
Productcode: FTL51C-
verklaring Number: EC_00548_03.17EU DeclarationDuits , Engels , fr -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
verklaring Number: EC_00559_03.17EU DeclarationDuits , Engels , fr -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
EU DeclarationDuits , Engels , fr -
Liquiphant M
Productcode: FTL51C-
verklaring Number: EC_00547_03.17EU DeclarationDuits , Engels , fr -
Liquiphant M
Productcode: FTL51C-
verklaring Number: EC_00545_03.17EU DeclarationDuits , Engels , fr -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
verklaring Number: EC_00546_03.17EU DeclarationDuits , Engels , fr -
Liquiphant M, Liquiphant S
Productcode: FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
verklaring Number: EC_00503_02.17EU DeclarationDuits , Engels , fr -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
verklaring Number: EG 01 007EU DeclarationDuits , Engels , fr -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
verklaring Number: EC_00455_03.16EU DeclarationDuits , Engels , fr -
SYSTEM, Prosonic S, Prosonic M, Micropilot S, Micropilot, Liquipoint T, Liquipoint, Liquiphant S, Liquiphant M, Liquiphant FailSafe, Liquiphant, Liquicap T, Liquicap M, Levelflex, Einstabsonde, Dreistabsonde, Doppelstabsonde
Productcode: FMR60-, FMR62-, FMU40-, FMU41-, FMU42-, FMU43-, FMU44-, FTI51-, FTI52-, FTL31-, FTL33-, FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-, FTL80-, FTL81-, FTL85-, FTW23-, FTW31-, FTW32-, FTW33-, NMR81-, NMR84-, FMR540-, 11362Z-, 11363Z-, 11371-, 11375Z-, 11961Z-, FDU90-, FDU91-, FDU91F-, FDU92-, FDU93-, FMI21-, FMI51-, FMI52-, FMP50-, FMP51-, FMP52-, FMP53-, FMP54-, FMP55-, FMR10-, FMR20-, FMR50-, FMR51-, FMR52-, FMR53-, FMR532-, FMR54-
Regio: Russia (TR CU), Russia (Declaration of Conformity)
Keuringsinstantie: EAC
Keurnummer: EAEC_N_C-DE.MU62.B.0006019MiscellaneousRussisch -
Liquiphant, Liquiphant FailSafe, Liquiphant M, Liquiphant S, Liquiphant T
Productcode: FTL85-, FTL81-, FTL80-, FTL71-, FTL70-, FTL51H-, FTL51C-, FTL51-, FTL50X-, FTL50H-, FTL50-, FTL330L-, FTL330H-, FTL33-, FTL31-, FTL260-, FTL20H-, FTL20-
Regio: Russia (TR CU)
Keuringsinstantie: EAC
Keurnummer: TС RU D-DE.MU62.B.02537MiscellaneousRussisch -
Liquiphant, Liquiphant FailSafe, Liquiphant M, Liquiphant S, Liquiphant T, Nivotester, Nivotester FailSafe
Productcode: FTL85-, FTL825-, FTL81-, FTL80-, FTL71-, FTL70-, FTL51H-, FTL51C-, FTL51-, FTL50H-, FTL50-, FTL375P-, FTL330L-, FTL330H-, FTL33-, FTL325P-, FTL325N-, FTL31-, FTL260-, FTL20H-, FTL20-, FTC325-
Regio: Russia (TR CU)
Keuringsinstantie: EAC
Keurnummer: TC № RU D-DE.AL32.B.07215MiscellaneousRussisch -
Liquiphant, Liquiphant FailSafe, Liquiphant M, Liquiphant S, Liquiphant T
Productcode: FTL85-, FTL81-, FTL80-, FTL71-, FTL70-, FTL51C-, FTL51-, FTL50H-, FTL50-, FTL33-, FTL31-, FTL20H-, FTL20-
Regio: Russia (TR CU)
Keuringsinstantie: EAC
Keurnummer: TC BY_112 11.01. TP020 003 127MiscellaneousRussisch -
SYSTEM, Pumpenschutz, Nivotester FailSafe, Nivotester, Micropilot S, Micropilot, Liquipoint T, Liquiphant T, Liquiphant S, Liquiphant M, Liquiphant FailSafe, Liquiphant, Liquicap T, Liquicap M, Levelflex, Floating Switch
Productcode: FTL260-, FTL31-, FTL325N-, FTL325P-, FTL33-, FTL375P-, FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-, FTL80-, FTL81-, FTL825-, FTL85-, FTS20-, FTW31-, FTW32-, FTW325-, FTW360-, NMR81-, NMR84-, FTI52-, FMI21-, FMI51-, FMI52-, FMP50-, FMP51-, FMP52-, FMP53-, FMP54-, FMP55-, FMR10-, FMR20-, FMR50-, FMR51-, FMR52-, FMR53-, FMR530-, FMR532-, FMR533-, FMR54-, FMR540-, FMR60-, FMR62-, FTC325-, FTI51-
Regio: Russia (Declaration of Conformity), Russia (TR CU)
Keuringsinstantie: EAC
Keurnummer: RU D-DE.MO10.B.05528MiscellaneousRussisch -
Liquiphant, Liquiphant FailSafe, Liquiphant M, Liquiphant S, Liquiphant T
Productcode: FTL20-, FTL20H-, FTL260-, FTL31-, FTL33-, FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Russia (TR CU)
Keuringsinstantie: EAC
Keurnummer: TC BY_112 11.01. TP004 003 127MiscellaneousRussisch -
SYSTEM, Pumpenschutz, Nivotester FailSafe, Nivotester, Micropilot S, Micropilot, Liquipoint T, Liquipoint, Liquiphant T, Liquiphant S, Liquiphant M, Liquiphant FailSafe, Liquiphant, Liquicap T, Liquicap M, Levelflex, Floating Switch, Einstabsonde, Dreistabsonde, Doppelstabsonde
Productcode: FTL70-, FTL51H-, FTL51C-, FTL51-, FTL50H-, FTL50-, FTL375P-, FTL33-, FTL325P-, FTL325N-, FTL31-, FTL260-, FTI52-, FTI51-, FTL71-, FTL80-, FTL81-, FTL825-, FTL85-, FTS20-, FTW23-, FTW31-, FTW32-, FTW325-, FTW33-, FTW360-, NMR81-, NMR84-, 11362Z-, 11363Z-, 11371-, 11375Z-, 11961Z-, FMI21-, FMI51-, FMI52-, FMP50-, FMP51-, FMP52-, FMP53-, FMP54-, FMP55-, FMR10-, FMR20-, FMR50-, FMR51-, FMR52-, FMR53-, FMR530-, FMR532-, FMR533-, FMR54-, FMR540-, FMR60-, FMR62-, FTC325-
Regio: Russia (Declaration of Conformity), Russia (TR CU)
Keuringsinstantie: EAC
Keurnummer: RU D-DE.MO10.B.05531MiscellaneousRussisch -
controller, Liquiphant M, Liquiphant S
Productcode: FML621-, FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Russia (TR CU)
Keuringsinstantie: EAC
Bescherming: Ex ib, Ex ia, Ex d e, Ex d, [Ex ia]Explosion ProtectionRussisch -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: Japan
Keuringsinstantie: DEKRAExplosion ProtectionJapans -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: USA, Canada
Keuringsinstantie: CSA
Catagorie: I,II,III/1/A,B,C,D,F,G/T6, I/zone 0
Bescherming: IS, AEx/Ex/ia/IIC/T6Explosion ProtectionEngels -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: International (IECEx)
Keuringsinstantie: DEKRA
Bescherming: Ex d IIB Ga/Gb, Ex d IIC Ga/Gb, Ex d e IIB Ga/Gb, Ex d e IIC Ga/GbExplosion ProtectionEngels -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: China
Keuringsinstantie: NEPSI
Catagorie: zone 0,1
Bescherming: Ex d IIB T6...T3 Ga/Gb, Ex d IIC T6...T3 Ga/Gb, Ex d e IIB T6...T3 Ga/Gb, Ex d e IIC T6...T3 Ga/GbExplosion ProtectionEngels , Chinees -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: USA
Keuringsinstantie: FM
Catagorie: I,II,III/1/A,B,C,D,E,F,G /T6
Bescherming: DIP, XPExplosion ProtectionEngels -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: Japan
Keuringsinstantie: DEKRA
Bescherming: Ex ia IIC T3 Ga/GbExplosion ProtectionJapans -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: USA, Canada
Keuringsinstantie: CSA
Catagorie: I,II,III/1,2/A,B,C,D,F,G
Bescherming: DIP, XPExplosion ProtectionEngels -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: International (IECEx)
Keuringsinstantie: DEKRA
Bescherming: Ex ia IIB Ga/Gb, Ex ia IIC Ga, Ex ia IIC Ga/Gb, Ex ia IIIC Da/DbExplosion ProtectionEngels -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL51H-, FTL50H-, FTL51-, FTL51C-, FTL70-, FTL71-
Regio: China
Keuringsinstantie: NEPSI
Bescherming: Ex iaD A20/21 IP6X T080°C, Ex ia IIB T6...T3 Ga/Gb, Ex ia IIC T6...T2 Ga/Gb, Ex ia IIC T6...T3 Ga/GbExplosion ProtectionEngels , Chinees -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: USA
Keuringsinstantie: FM
Catagorie: I/2/A,B,C,D/T5, I,II,III/1/A,B,C,D,E,F,G/T5, II,III/2/F,G/T5, I/zone 0
Bescherming: IS, NI, S, AEx ia IIC T5Explosion ProtectionEngels -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: USA, Canada
Keuringsinstantie: CSA
Catagorie: I,II,III/1/A,B,C,D,F,G/T6, I/zone 0
Bescherming: IS, AEx/Ex/ia/IIC/T6Explosion ProtectionEngels -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Brazil
Keuringsinstantie: INMETRO
Catagorie: zone 0,1
Bescherming: Ex d IIB Txxx°C Ga/Gb, Ex d IIC Txxx°C Ga/GbExplosion ProtectionPortugees -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Brazil
Keuringsinstantie: INMETRO
Catagorie: zone 0,1, zone 20,21
Bescherming: Ex ia IIB Txxx°C Ga/Gb, Ex ia IIC Txxx°C Ga/Gb, Ex ia IIIC Txxx°C Da/DbExplosion ProtectionPortugees -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Europe (ATEX)
Keuringsinstantie: DEKRA
Catagorie: II 1/2 G
Bescherming: Ex d IIB Ga/Gb, Ex d IIC Ga/Gb, Ex d e IIB Ga/Gb, Ex d e IIC Ga/GbExplosion ProtectionEngels -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Europe (ATEX)
Keuringsinstantie: DEKRA
Catagorie: II 1/2 D, II 1/2 G, II 1 G
Bescherming: Ex ia IIB T6 Ga/Gb, Ex ia IIC T6 Ga, Ex ia IIC T6 Ga/Gb, Ex ia IIIC Da/DbExplosion ProtectionEngels -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Brazil
Keuringsinstantie: INMETRO
Catagorie: zone 0,1, zone 20,21
Bescherming: Ex ia IIB Txxx°C Ga/Gb, Ex ia IIC Txxx°C Ga/Gb, Ex ia IIIC Txxx°C Da/DbExplosion ProtectionPortugees -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Europe (ATEX)
Keuringsinstantie: Endress+Hauser
Catagorie: II 3 D, II 3 G
Bescherming: Ex ic IIC T6...T2 Gc, Ex ic IIC T6...T3 Gc, Ex nA IIC T6...T2 Gc, Ex nA IIC T6...T3 Gc, Ex nC IIC T6...T2 Gc, Ex nC IIC T6...T3 Gc, IIIC T085°C DcExplosion ProtectionDuits , Engels , fr -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: China
Keuringsinstantie: NEPSI
Catagorie: zone 2
Bescherming: Ex ic IIC T6...T3 GcExplosion ProtectionEngels , Chinees -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Brazil
Keuringsinstantie: INMETRO
Catagorie: zone 0,1
Bescherming: Ex d e IIB Txxx°C Ga/Gb, Ex d e IIC Txxx°C Ga/GbExplosion ProtectionPortugees -
Liquiphant M
Productcode: FTL51H-, FTL51C-, FTL51-, FTL50H-, FTL50-
Regio: China
Keuringsinstantie: NEPSI
Catagorie: zone 0,1
Bescherming: Ex d IIB T6...T3 Ga/Gb, Ex d IIC T6...T3 Ga/Gb, Ex d e IIB T6...T3 Ga/Gb, Ex d e IIC T6...T3 Ga/GbExplosion ProtectionEngels , Chinees -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Brazil
Keuringsinstantie: INMETRO
Catagorie: zone 0,1, zone 20,21
Bescherming: Ex ia IIB Txxx°C Ga/Gb, Ex ia IIC Txxx°C Ga/Gb, Ex ia IIIC Txxx°C Da/DbExplosion ProtectionPortugees -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51H-, FTL51-, FTL51C-
Regio: China
Keuringsinstantie: NEPSI
Bescherming: Ex nA, Ex nCExplosion ProtectionEngels , Chinees -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Brazil
Keuringsinstantie: INMETRO
Catagorie: zone 0,1
Bescherming: Ex d IIB Txxx°C Ga/Gb, Ex d IIC Txxx°C Ga/GbExplosion ProtectionPortugees -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: Japan
Keuringsinstantie: DEKRA
Bescherming: Ex ia IIC T3 Ga/GbExplosion ProtectionJapans -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: Japan
Keuringsinstantie: DEKRA
Bescherming: Ex db IIB T3 Ga/GbExplosion ProtectionJapans -
Nivotester, Liquiphant M, Liquiphant S
Productcode: FTL51-, FTL50-, FTL50H-, FTL51H-, FTL51C-, FTL71-, FTL70-, SIN110-, SIF111-, SIF101-, RN221-, RMA421-, RIA250-, FXN422-, FXN421-, FTL375P-, FTL375N-, FTL372-, FTL370-, FTL325P-, FTL325N-, FTL320-, FTL120Z-, FTL170Z-
Regio: Germany
Keuringsinstantie: DIBt
Keurnummer: Z-65.11-230Overfill PreventionDuits -
Liquiphant M, Liquiphant S, Nivotester
Productcode: SIN110-, SIF111-, SIF101-, RN221-, RMA422-, RMA421-, RIA450-, RIA250-, FXN422-, FXN421-, FTL71-, FTL70-, FTL51H-, FTL51C-, FTL51-, FTL50H-, FTL50-, FTL375P-, FTL375N-, FTL372-, FTL370-, FTL325P-, FTL325N-, FTL320-, FTL170Z-, FTL120Z-
Regio: Germany
Keuringsinstantie: DIBt
Keurnummer: Z-65.40-446Overfill PreventionDuits -
Liquiphant M
Productcode: FTL50-, FTL51-, FTL51C-
Regio: Switzerland
Keuringsinstantie: SVTI
Keurnummer: 321.007.16Overfill PreventionDuits -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Switzerland
Keuringsinstantie: SVTI
Keurnummer: 302.005.15Overfill PreventionDuits -
Liquiphant, Liquiphant FailSafe, Liquiphant M, Liquiphant S
Productcode: FTL85-, FTL81-, FTL80-, FTL71-, FTL70-, FTL51H-, FTL51C-, FTL51B-, FTL51-, FTL50H-, FTL50-, FTL41-
Regio: Canada (CRN)
Keuringsinstantie: CRNPressure EquipmentEngels -
Micropilot S, Liquiphant S, Levelflex, Micropilot, Liquiphant M, Minicap, Nivector, Prosonic M, Prosonic S, Prosonic T, Pumpenschutz, Solicap M, Solicap S, Soliphant M, Soliphant T, SYSTEM, Liquipoint T, Liquipoint, Liquiphant FailSafe, Liquiphant, Liquicap T, Liquicap M, Einstabsonde, Dreistabsonde, Doppelstabsonde
Productcode: FTL51-, FMP54-, FMP52-, FMR52-, FMR54-, FMP57-, FMP55-, FMP51-, FMR51-, FMR57-, FMP53-, FMR56-, FMP56-, FMR53-, FMR50-, FMP50-, FMU41-, FMU42-, FTL51H-, FTL50H-, FMU43-, FMU44-, FTL51C-, FTL70-, FMU40-, FMI52-, FTL50-, FTL71-, FTM51-, FTI52-, FMR532-, FTL81-, FMI51-, FMR533-, FTI51-, FTL85-, FTM52-, FTL33-, FTL31-, FTI77-, FTI56-, FTI55-, FTC968Z-, FTC262-, FTC260-, FTL80-, FTM20-, FTM21-, FTM50-, FTW23-, FTW31-, FTW32-, FTW33-, FTW360-, NMR84-, NMR81-, 11263-, 11362Z-, 11363Z-, 11375Z-, 11961Z-, FDU90-, FDU91-, FDU91F-, FDU92-, FDU95-, FDU96-, FDU93-, FMI21-, FMU30-, FMR540-, FMR530-, FMR10-, FMR20-
Keuringsinstantie: TÜVPressure EquipmentDuits , Engels -
Liquiphant M, contactors / transmitters, controller
Productcode: FTL51H-, FTL50H-, FTL51-, FTL51C-, FTL50-, FML621-
Regio: Russia
Keuringsinstantie: Rosstandart
Keurnummer: OC.C.31.004.A_35819/1MetrologyRussisch -
controller, Liquiphant M
Productcode: FML621-, FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: Kazakhstan
Keuringsinstantie: KazInMetr
Keurnummer: 12132MetrologyRussisch -
controller, Liquiphant M
Productcode: FML621-, FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: Belarus
Keuringsinstantie: BEL
Keurnummer: 11103MetrologyRussisch -
Liquiphant M, Liquiphant S, Nivotester
Productcode: FTL51C-, FTL51H-, FTL70-, FTL71-, FTL51-, FEL57-, FTL375P-, FTL50-, FTL50H-
Regio: International
Keuringsinstantie: TÜV
SIL: SIL2/3
Veiligheidsfunctie:Safety Integrity Level (SIL)Duits , Engels -
Liquiphant M, Liquiphant S, Nivotester
Productcode: FTL51C-, FTL51H-, FTL70-, FTL71-, FTL51-, FEL57-, FTL325P-, FTL50-, FTL50H-
Regio: International
Keuringsinstantie: TÜV
SIL: SIL2/3
Veiligheidsfunctie:Safety Integrity Level (SIL)Duits , Engels -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: International
Keuringsinstantie: ABSMarineEngels -
Liquiphant M
Productcode: FTL51H-, FTL50-, FTL50H-, FTL51-, FTL51C-
Regio: South Korea
Keuringsinstantie: KRMarineEngels -
Liquiphant M
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-
Regio: International
Keuringsinstantie: DNVGLMarineEngels -
Liquiphant FailSafe, Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL51-, FTL51C-, FTL70-, FTL71-, FTL80-, FTL81-, FTL85-
Regio: International
Keuringsinstantie: RM RSMarineRussisch -
Liquiphant M, Liquiphant S
Productcode: FTL50-, FTL50H-, FTL51-, FTL51C-, FTL51H-, FTL70-, FTL71-
Regio: Canada, USA
Keuringsinstantie: CSAOrdinary Location Product SafetyEngels
Accessoires / Spare parts
-
-
Nr 20 Order code 52002698
Deksel voor alu. F13 behuizing
Alu deksel met O-ring EPDM voor F13 huis
-
Nr 20 Order code 52002699
Deksel voor alu. F17 behuizing
Met EPDM O-ring t.b.v. aluminium F17 behuizing
-
Nr 20 Order code 52005266
FTL5X RVS DEKSEL MET WAARS.STICKER
Voor RVS behuizing 316L, LIQUIPHANT M
-
Nr 20 Order code 52006903
Cover T13 Alu, gasket EPDM
O-ring EPDM. Gebruik: Behuizing T13 Aluminium.
-
Nr 20 Order code 52025606
Deksel F16, grijs, PBTP, incl. O-ring
Pakking EPDM. Gebruik: behuizing F16 Polyester, FMI21, FMI51/FMI52, FMU30, FTI51/FTI52/ FTI55/FTI56, FTI77, FTL50/FTL51/FTL51C/ FTL51H, FTL70/FTL71, FTL80/FTL81/FTL85, FTW31/FTW32.
-
Nr 20 Order code 52025790
Deksel F16 transparant met afdichting
Gasket EPDM. Usage: housing F16 Polyester.
-
Nr 20 Order code 52027000
Deksel voor 316L F15 behuizing
Met dichtring 67,5x2,9x1,5, VMQ/PTFE voor RVS behuizing F15
-
Nr 20 Order code 52027002
Cover F15 316L, sight glass, gasket
Sight glass: glass. Gasket 67.5x2.9x1.5, VMQ/PTFE. Usage: housing F15, stainless steel.
-
Nr 20 Order code 52028207
Cover F15, sight glass PC, 316L, gasket
Display glas van polycarbonaat Afdichtingsring 67,5x2,9x1,5 VMQ/PTFE Voor gebruik in explosie veilig gebied Geen ATEX RSV huis F15
-
Nr 20 Order code 71114754
Cover F27 316L, gasket EPDM
Material: 316L. O-ring 70.0x3.0 EPDM. Usage: stainless steel housing F27, FTL50/FTL51/FTL51C, FTL70/FTL71, FTL80/FTL81/FTL85.
-
-
-
Nr 12 Order code 52004236
FTL7X bevestigingset voor behuizing
bestaande uit: veiligheidsring SS304 adapter ring PPA
-
-
-
Nr 21 Order code 52004137
-
Nr 21 Order code 52004277
FTL7X deksel afdichting F13 (10 stuks)
Bestaand uit: 10 x O-ring 70.0 x3.0 EPDM
-
Nr 21 Order code 52008495
-
Nr 21 Order code 52028179
Afdichting 67,5x2,9x1,5 VMQ/PTFE 5st.
Geprofileerde dichtringen voor deksel van RVS F15 behuizing.
-
Nr 21 Order code 71114756
Sealing set FVQM, cover F27, 3 pc.
Bestaat uit: 3x O-ring 70.0x3.0 FVQM.
-
-
-
Nr 15 Order code 52002447
FTL5x adapter G1/2 voor F15 behuizing
Bestaat uit: Adapter M20> G1/2,316. Pakking NBR. Blinde plug G1/2. Gebruik: PMC41/PMC45, PMP41/PMP45/PMP46,FTL50/FTL50H/ FTL51/FTL51H/FTL51C,FTL70/FTL71, FTL80/FTL81/FTL85.
-
Nr 15 Order code 52002448
FTL5x adapter NPT1/2 voor F15 behuizing
Bestaat uit: Adapter M20> NPT1/2,316. Pakking NBR. Plug NPT1/2. Gebruik: PMC41/PMC45, PMP41/PMP45/PMP46,FTL50/FTL50H/ FTL51/FTL51H/FTL51C,FTL70/FTL71, FTL80/FTL81/FTL85.
-
Nr 15 Order code 52004133
FTL7X adapterset voor wartel NPT 1/2"
voor polyester behuizing F16 LIQUIPHANT M
-
Nr 15 Order code 52004134
-
Nr 15 Order code 52004135
FTL7X adapterset voor wartel G 1/2
voor polyester huis F16 LIQUIPHANT M
-
Nr 15 Order code 52004278
FTL5x wartel M20 voor F15 behuizing
Bestaat uit: Kabelwartel M20. O-ring EPDM. Gebruik: FTL50/FTL50H / FTL51/FTL51H/FTL51C, FTL70/FTL71, FTL80/FTL81/FTL85.
-
-
-
Nr 25 Order code 52007103
Cover T13 "Terminal" Alu, gasket EPDM
O-ring EPDM. Gebruik: Terminal compartiment, Behuizing T13 Aluminium.
-
-
-
Nr 30 Order code 52002304
-
Nr 30 Order code 52002305
Electronics FEL52 10-55VDC-PNP
voor LIQUIPHANT M 3 draads: PNP 10....55V DC
-
Nr 30 Order code 52002306
-
Nr 30 Order code 52002307
-
Nr 30 Order code 52002308
FTL5x FEL56
Niveauschakelaar 2-draads. Hardwareversie 01.01. Softwareversie 01.00.01. Gebruik: FTL50/FTL50H/FTL51/FTL51C/FTL51H, FTL70/FTL71.
-
Nr 30 Order code 52002309
-
Nr 30 Order code 52006454
FTL5X FEL58
Level switch 2-wire + push button. Hardware version 01.02. Software version 01.00.01. Usage: Liquiphant M/S (HT).
-
Nr 30 Order code 71027201
Electronics FEL50D Density/Concentration
Hardware versie 01.00. Software versie 01.00.00. Gebruik: FTL50/FTL50H/FTL51/FTL51C/FTL51H + FML621. Niet voor WHG.
-
Nr 30 Order code 71074953
Electronica FEL50A,PA,HW02.00,SW01.03.00
PROFIBUS PA. Hardware versie 02.00. Software versie 01.03.00. 12,5mA+/-1,0mA. Liquiphant M/S (HT).
-
-
-
Order code 52005977
Lubricant "SYNTHESO GLEP1" (tube a 8g)
-
Order code 71127760
Zonnekap/beschermkap F16 behuizing
Usage: FDR56, FMI21, FMI51/FMI52, FQR56, FTI51/FTI52/FTI55/FTI56, FTI77, FTL50/FTL50H/FTL51/FTL51C/FTL51H, FTL70/FTL71, FTL80/FTL81/FTL85, FTM20/FTM21, FTM50/FTM51/FTM52, FTR20, FTW31/FTW32/FTW33.
-
Order code 71040497
Weerbestendige deksel F13/F17/F18/F27
Gebruik: FMI51/FMI52, FTI51/FTI52/FTI55/FTI56, FTI77, FTL50/FTL50H/FTL51/FTL51C/FTL51H, FTL70/FTL71, FTL80/FTL81/FTL85, FTM20/FTM21, FTM50/FTM51/FTM52.
-
Order code 71067434
Modificatietypeplaat, non Ex
Blanco. Te voorzien van een nieuwe typecodering wanneer een non Ex instrument gemodificeerd is.
-
-
Voorganger